FR100 Specifications Print E-mail
INPUTS
Configurations:

 

8 Analogue, 16 Digital.

16 Analogue, 32 Digital.

24 Analogue, 48 Digital.

32 Analogue, 64 Digital.

Analogue channels selectable for voltage or current measurement.

Nominal Voltage:63.5 or 110V AC (other levels available).
Nominal Current:

1 or 5A AC via external resistive shunt (other levels available).

Measurement Range:Typically nominal voltage x1.9, nominal current x20 (other ranges available).
Analogue Bandwidth: DC - 3kHz.
A/D Resolution:12 bits (optionally 16 bits).
Analogue Accuracy: Better than 0.25% of measurement range.
Digital:24 - 250V DC normally open or closed wet contacts with adjustable debounce filtering.
FAULT RECORDING 
Sample Rate:Up to 192 samples per cycle (9.6kHz on a 50Hz system, 11.52kHz on a 60Hz system).
Pre-Fault Time:34ms to 1s.
Post Fault Time:134ms to 1s.
Fault Time:Recording can be extended up to 5s with operation limiter on longer fault/trigger conditions.
Synchronisation:All inputs sampled simultaneously.
Data Storage:Buffer memory (RAM) with auto-transfer to non-volatile mass memory device.
FAULT TRIGGERING 
Analogue:

Over / under level equipped with hysteresis.

Rate of change of level.

Over / under frequency (1 per 8 analogue channels).

Trigger Accuracy:Better than 2%
Digital:On alarm with option for return to normal.
Multiple Recorders:Recorders can be inter-triggered to form larger systems.
REAL TIME CLOCK 
Range:Time, date, leap year and day of the year with internal battery backup.
Resolution:1mSec.
Accuracy:Better than 1s per day (free running internal clock).
Synchronisation:

1 pulse per second, minute or hour.

IRIG-B time code (optional).

DCF-77 radio signal (optional). Limited signal availability.

GPS satellite signal (optional).

COMMUNICATIONS 
Local:RS232 direct connection to local PC.
Remote:Modem connection to remotely located PC (optional).
Network:Ethernet connection using TCP/IP protocol to PC.
LOCAL PRINTOUT 
Connection:Parallel printer port.
Compatibility:Epson compatible 9 and 24 pin dot matrix parallel printer.
GENERAL

 

 

Visual Indication:Front panel LED’s for Power Healthy, System Armed, New Fault Records, Communications and Attention (Common Diagnostics Alarm).

Contact Outputs:

Volt-free normally open or closed system status contact for remote indication for Power Healthy, System Armed, Recorder Triggered (auto reset) and Attention (Common Diagnostics Alarm).
Optional Built-in PC:VGA Colour ‘high bright’ TFT display with PS/2 connections for an external keyboard with built in trackball.
OPERATING VOLTAGES 
Prime Power:100 to 350V DC, 88 to 264V AC auto-sensing via IEC power connection.
Burden:<60 VA load.
ENVIRONMENTAL 

Operating Temperature:

-20ºC to +60ºC (-4ºF to +140ºF)
Humidity:0 to 97% RH non-condensing.
Isolation:2kV rms for 1 minute (channel to channel, channel to earth).

Surge Withstand Transient:

To IEC 801-5. 1.2/50mS.

Common Mode: Severity level class 4.

Series Mode: Severity level class 3.

Fast Transient Burst:To IEC 801-4 level 3.
RFI Immunity:To IEC801-3 level 3. 10V/m 26-1000MHz.
Emissions:To EN50081-1: 1992.
MECHANICAL DETAILS 
Enclosure:6U steel enclosure suitable for Euro 19” wide rack mounting or free standing (tabletop).
Ventilation:Fan assisted.
Terminals:Rear access screw compression type - up to 1.5sq mm.
Weight:<15kg.
DUE TO CONTINUING DEVELOPMENT AND IMPROVEMENTS WEIS RESERVES THE RIGHT TO CHANGE THIS SPECIFICATION WITHOUT NOTICE